On-site generation
Every air permit in the public record for the data centers we track, project by project. Each permit states the backup generation that stands behind its site in its own terms: how many engines, of what kind, and sometimes the fleet's capacity in megawatts. The figures are printed exactly as the permit states them, with the permit named on the row.
Every data center runs on backup power, and the air permit is where the size of that backup becomes a public number: the permit names the engines that stand behind the site. We hold 237 air permits for 195 of the 1320 projects we track. 88 of those permits state how many generators stand behind the site, and 44 state the generator fleet's capacity in megawatts. This page lists every permit and prints each figure exactly as the permit states it. The figures are never added together: a project can hold several permits, and one fleet can be named under more than one of them. The other 1125 projects hold no air permit in any record we have found.
Meta Huntsville Data Center
Huntsville, Alabama · 2 air permits
City of Huntsville Natural Resources Division
- Status
- Under review
- What the permit states
- This permit states no generator count or capacity in the record we hold.
City of Huntsville Natural Resources Division
- Status
- Issued
- What the permit states
- This permit states no generator count or capacity in the record we hold.
| Permit | Status | What the permit states |
|---|---|---|
| City of Huntsville Natural Resources Division | Under review | This permit states no generator count or capacity in the record we hold. |
| City of Huntsville Natural Resources Division | Issued | This permit states no generator count or capacity in the record we hold. |
Microsoft San Jose data center (Alviso)
San Jose, California · 2 air permits
Bay Area Air Quality Management District, Air District Application #31953; Sources S-1 through S-140
- Status
- Issued · Decided April 3, 2025
- What the permit states
- This permit states no generator count or capacity in the record we hold.
Bay Area Air Quality Management District, Air District Application 704043; 84 generators (document numbering: Sources S-7 through S-90)
- Status
- Issued · Decided August 18, 2026
- What the permit states
- This permit states no generator count or capacity in the record we hold.
| Permit | Status | What the permit states |
|---|---|---|
| Bay Area Air Quality Management District, Air District Application #31953; Sources S-1 through S-140 | IssuedDecided April 3, 2025 | This permit states no generator count or capacity in the record we hold. |
| Bay Area Air Quality Management District, Air District Application 704043; 84 generators (document numbering: Sources S-7 through S-90) | IssuedDecided August 18, 2026 | This permit states no generator count or capacity in the record we hold. |
EdgeConneX Denver Campus
Englewood, Colorado · 1 air permit
Colorado Department of Public Health and Environment, Air Pollution Control Division, 25DG0038 (Issuance 1)
- Status
- Issued · Decided February 23, 2026
- What the permit states
- Generators: 8 diesel-fueled internal combustion emergency engines (AIRS Point 001), MTU model 12V1600 DS550, design rating 822 horsepower eachGenerators: 1 diesel-fueled internal combustion emergency engine (AIRS Point 002), CAT model C18, design rating 900 horsepowerGenerators: 15 diesel-fueled internal combustion emergency engines with selective catalytic reduction controls (AIRS Point 004), CAT model 3516C, design rating 3,147 horsepower eachGenerators: 3 diesel-fueled internal combustion emergency engines (AIRS Point 003), CAT model 3516C, design rating 3,147 horsepower each
| Permit | Status | What the permit states |
|---|---|---|
| Colorado Department of Public Health and Environment, Air Pollution Control Division, 25DG0038 (Issuance 1) | IssuedDecided February 23, 2026 | Generators: 8 diesel-fueled internal combustion emergency engines (AIRS Point 001), MTU model 12V1600 DS550, design rating 822 horsepower eachGenerators: 1 diesel-fueled internal combustion emergency engine (AIRS Point 002), CAT model C18, design rating 900 horsepowerGenerators: 15 diesel-fueled internal combustion emergency engines with selective catalytic reduction controls (AIRS Point 004), CAT model 3516C, design rating 3,147 horsepower eachGenerators: 3 diesel-fueled internal combustion emergency engines (AIRS Point 003), CAT model 3516C, design rating 3,147 horsepower each |
Microsoft FTY01 (Douglasville)
Douglasville, Georgia · 1 air permit
Georgia Environmental Protection Division, Air Protection Branch, Permit No. 7376-097-0097-S-01-0 (Application No. 28295; AIRS No. 04-13-097-00097)
- Status
- Issued · Decided October 13, 2022
- What the permit states
- Generator capacity: 60.5 MW
| Permit | Status | What the permit states |
|---|---|---|
| Georgia Environmental Protection Division, Air Protection Branch, Permit No. 7376-097-0097-S-01-0 (Application No. 28295; AIRS No. 04-13-097-00097) | IssuedDecided October 13, 2022 | Generator capacity: 60.5 MW |
Google Council Bluffs data center campus
Council Bluffs, Iowa · 1 air permit
Iowa Department of Natural Resources, Air Quality Bureau, Title V Operating Permit 16-TV-002R1; Facility File (Plant) No. 78-01-121; EIQ No. 92-6982
- Status
- Issued · Decided September 7, 2021
- What the permit states
- Generators: 361 emergency diesel engines
| Permit | Status | What the permit states |
|---|---|---|
| Iowa Department of Natural Resources, Air Quality Bureau, Title V Operating Permit 16-TV-002R1; Facility File (Plant) No. 78-01-121; EIQ No. 92-6982 | IssuedDecided September 7, 2021 | Generators: 361 emergency diesel engines |
Meta Altoona Data Center
Altoona, Iowa · 1 air permit
Iowa Department of Natural Resources, Air Quality Bureau, Title V Operating Permit 18-TV-007R1; Facility File No. 77-07-010; EIQ No. 92-6988
- Status
- Issued · Decided April 8, 2024
- What the permit states
- Generators: 112 emergency diesel generatorsGenerator capacity: 328 MW
| Permit | Status | What the permit states |
|---|---|---|
| Iowa Department of Natural Resources, Air Quality Bureau, Title V Operating Permit 18-TV-007R1; Facility File No. 77-07-010; EIQ No. 92-6988 | IssuedDecided April 8, 2024 | Generators: 112 emergency diesel generatorsGenerator capacity: 328 MW |
Microsoft Project Ginger East (West Des Moines)
West Des Moines, Iowa · 1 air permit
Iowa Department of Natural Resources, 24-TV-005
- Status
- Issued · Decided December 9, 2024
- What the permit states
- Generators: 128 emergency diesel engines
| Permit | Status | What the permit states |
|---|---|---|
| Iowa Department of Natural Resources, 24-TV-005 | IssuedDecided December 9, 2024 | Generators: 128 emergency diesel engines |
Microsoft Project Ginger West (West Des Moines)
West Des Moines, Iowa · 1 air permit
Iowa Department of Natural Resources, 26-TV-003
- Status
- Issued · Decided April 10, 2026
- What the permit states
- Generators: 126 emergency diesel engines
| Permit | Status | What the permit states |
|---|---|---|
| Iowa Department of Natural Resources, 26-TV-003 | IssuedDecided April 10, 2026 | Generators: 126 emergency diesel engines |
Microsoft Project Osmium (West Des Moines)
West Des Moines, Iowa · 1 air permit
Iowa Department of Natural Resources, 24-TV-004
- Status
- Issued · Decided October 17, 2024
- What the permit states
- Generators: 104 emergency diesel engines
| Permit | Status | What the permit states |
|---|---|---|
| Iowa Department of Natural Resources, 24-TV-004 | IssuedDecided October 17, 2024 | Generators: 104 emergency diesel engines |
Meta Sarpy County Data Center
Springfield, Nebraska · 1 air permit
Nebraska Department of Environment and Energy, FID 108432
- Status
- Under review · Filed January 8, 2025
- What the permit states
- This permit states no generator count or capacity in the record we hold.
| Permit | Status | What the permit states |
|---|---|---|
| Nebraska Department of Environment and Energy, FID 108432 | Under reviewFiled January 8, 2025 | This permit states no generator count or capacity in the record we hold. |
Amazon Storey County Data Center (Peru Drive)
Sparks, Nevada · 1 air permit
Nevada Division of Environmental Protection, Bureau of Air Pollution Control, AP7374-4768 (FIN A2648)
- Status
- Under review
- What the permit states
- This permit states no generator count or capacity in the record we hold.
| Permit | Status | What the permit states |
|---|---|---|
| Nevada Division of Environmental Protection, Bureau of Air Pollution Control, AP7374-4768 (FIN A2648) | Under review | This permit states no generator count or capacity in the record we hold. |
Apple Reno data center
Sparks, Nevada · 1 air permit
Northern Nevada Public Health, Air Quality Management Division, AAIR16-0082
- Status
- Issued · Decided June 13, 2025
- What the permit states
- Generators: 40 enginesGenerator capacity: 137 MW
| Permit | Status | What the permit states |
|---|---|---|
| Northern Nevada Public Health, Air Quality Management Division, AAIR16-0082 | IssuedDecided June 13, 2025 | Generators: 40 enginesGenerator capacity: 137 MW |
Colovore RNO01
Storey County, Nevada · 1 air permit
Nevada Division of Environmental Protection, Bureau of Air Pollution Control, AP7374-5002 (Facility ID A2675)
- Status
- Under review
- What the permit states
- Generators: 5 emergency standby generators (S2.001 through S2.005), Rolls-Royce Solutions America model 20V4000G94S, 3,490 kW each, manufactured 2024
| Permit | Status | What the permit states |
|---|---|---|
| Nevada Division of Environmental Protection, Bureau of Air Pollution Control, AP7374-5002 (Facility ID A2675) | Under review | Generators: 5 emergency standby generators (S2.001 through S2.005), Rolls-Royce Solutions America model 20V4000G94S, 3,490 kW each, manufactured 2024 |
EdgeCore Reno Campus
Storey County, Nevada · 1 air permit
Nevada Division of Environmental Protection, Bureau of Air Pollution Control, AP7374-4772 (FIN A2652)
- Status
- Under review
- What the permit states
- This permit states no generator count or capacity in the record we hold.
| Permit | Status | What the permit states |
|---|---|---|
| Nevada Division of Environmental Protection, Bureau of Air Pollution Control, AP7374-4772 (FIN A2652) | Under review | This permit states no generator count or capacity in the record we hold. |
Novva Tahoe Reno
Storey County, Nevada · 1 air permit
Nevada Division of Environmental Protection, Bureau of Air Pollution Control, AP7374-4667 (FIN A2569)
- Status
- Issued
- What the permit states
- This permit states no generator count or capacity in the record we hold.
| Permit | Status | What the permit states |
|---|---|---|
| Nevada Division of Environmental Protection, Bureau of Air Pollution Control, AP7374-4667 (FIN A2569) | Issued | This permit states no generator count or capacity in the record we hold. |
Switch Citadel Campus (TAHOE RENO)
Storey County, Nevada · 1 air permit
Nevada Division of Environmental Protection, Bureau of Air Pollution Control, Class I Operating Permit to Construct AP7375-3672; Facility ID No. A1896
- Status
- Issued · Decided December 30, 2015
- What the permit states
- Generators: 1 diesel-fired emergency generator (System 09, S2.003), Kohler/Rehlko model 350REOZJC Diesel, 538 hp, year 2025
| Permit | Status | What the permit states |
|---|---|---|
| Nevada Division of Environmental Protection, Bureau of Air Pollution Control, Class I Operating Permit to Construct AP7375-3672; Facility ID No. A1896 | IssuedDecided December 30, 2015 | Generators: 1 diesel-fired emergency generator (System 09, S2.003), Kohler/Rehlko model 350REOZJC Diesel, 538 hp, year 2025 |
Sentinel PN-DC1 South Brunswick
South Brunswick township, New Jersey · 1 air permit
New Jersey Department of Environmental Protection, Bureau of Stationary Sources, PCP250001 (Program Interest No. 19525)
- Status
- Under review · Filed August 20, 2026
- What the permit states
- Generators: 12 generatorsGenerator capacity: 43.44 MW
| Permit | Status | What the permit states |
|---|---|---|
| New Jersey Department of Environmental Protection, Bureau of Stationary Sources, PCP250001 (Program Interest No. 19525) | Under reviewFiled August 20, 2026 | Generators: 12 generatorsGenerator capacity: 43.44 MW |
NTT Hillsboro data center campus
Hillsboro, Oregon · 2 air permits
Oregon Department of Environmental Quality, Northwest Region, Permit No. 34-0235-ST-01; Application No. 031135
- Status
- Expired · Filed January 29, 2020
- What the permit states
- Generators: 1 enginesGenerators: 44 enginesGenerator capacity: 144.5 MW
Oregon Department of Environmental Quality, Northwest Region, Addendum R-02 to Permit No. 34-0235-ST-01; Application No. 33100
- Status
- Expired · Decided May 13, 2021
- What the permit states
- This permit states no generator count or capacity in the record we hold.
| Permit | Status | What the permit states |
|---|---|---|
| Oregon Department of Environmental Quality, Northwest Region, Permit No. 34-0235-ST-01; Application No. 031135 | ExpiredFiled January 29, 2020 | Generators: 1 enginesGenerators: 44 enginesGenerator capacity: 144.5 MW |
| Oregon Department of Environmental Quality, Northwest Region, Addendum R-02 to Permit No. 34-0235-ST-01; Application No. 33100 | ExpiredDecided May 13, 2021 | This permit states no generator count or capacity in the record we hold. |
QTS Hillsboro data center campus
Hillsboro, Oregon · 1 air permit
Oregon Department of Environmental Quality, Permit No. 34-0222-ST-01, Addendum No. 5 (Application No. 034858)
- Status
- Issued · Decided October 16, 2023
- What the permit states
- This permit states no generator count or capacity in the record we hold.
| Permit | Status | What the permit states |
|---|---|---|
| Oregon Department of Environmental Quality, Permit No. 34-0222-ST-01, Addendum No. 5 (Application No. 034858) | IssuedDecided October 16, 2023 | This permit states no generator count or capacity in the record we hold. |
Amazon data center campus (Falls Township)
Falls Township, Pennsylvania · 3 air permits
Pennsylvania Department of Environmental Protection, Plan Approval 09-0261
- Status
- Issued · Decided July 25, 2025
- What the permit states
- Generators: 72 diesel-fired critical emergency generator engines rated 2.75 MW each (CEG1 through CEG72)Generators: 4 diesel-fired house emergency generator engines (two at 1,000 kW and two at 750 kW)Generator capacity: 198 MW (72 engines at 2.75 MW each; backup generator capacity, not campus IT load)Generator capacity: 3.5 MW (2 x 1,000 kW plus 2 x 750 kW house emergency engines)
Pennsylvania Department of Environmental Protection, Minor Plan Approval Modification of 09-0261
- Status
- Issued · Decided November 24, 2025
- What the permit states
- This permit states no generator count or capacity in the record we hold.
Pennsylvania Department of Environmental Protection, Proposed Plan Approval 09-0261A
- Status
- Under review · Filed April 2026
- What the permit states
- Generators: 280 natural gas-fired critical back-up generator engines rated 4,287 hp each (NGG1 through NGG280)Generators: 3 diesel-fired ancillary emergency generator engines (one 2,360 hp Tier 2, one 609 hp Tier 3, one 398 hp Tier 3)
| Permit | Status | What the permit states |
|---|---|---|
| Pennsylvania Department of Environmental Protection, Plan Approval 09-0261 | IssuedDecided July 25, 2025 | Generators: 72 diesel-fired critical emergency generator engines rated 2.75 MW each (CEG1 through CEG72)Generators: 4 diesel-fired house emergency generator engines (two at 1,000 kW and two at 750 kW)Generator capacity: 198 MW (72 engines at 2.75 MW each; backup generator capacity, not campus IT load)Generator capacity: 3.5 MW (2 x 1,000 kW plus 2 x 750 kW house emergency engines) |
| Pennsylvania Department of Environmental Protection, Minor Plan Approval Modification of 09-0261 | IssuedDecided November 24, 2025 | This permit states no generator count or capacity in the record we hold. |
| Pennsylvania Department of Environmental Protection, Proposed Plan Approval 09-0261A | Under reviewFiled April 2026 | Generators: 280 natural gas-fired critical back-up generator engines rated 4,287 hp each (NGG1 through NGG280)Generators: 3 diesel-fired ancillary emergency generator engines (one 2,360 hp Tier 2, one 609 hp Tier 3, one 398 hp Tier 3) |
CoreWeave data center (Lancaster)
Lancaster, Pennsylvania · 2 air permits
Pennsylvania Department of Environmental Protection, 36-05169A
- Status
- Issued · Decided December 29, 2025
- What the permit states
- This permit states no generator count or capacity in the record we hold.
Pennsylvania Department of Environmental Protection, 36-05169B
- Status
- Under review · Filed June 22, 2026
- What the permit states
- This permit states no generator count or capacity in the record we hold.
| Permit | Status | What the permit states |
|---|---|---|
| Pennsylvania Department of Environmental Protection, 36-05169A | IssuedDecided December 29, 2025 | This permit states no generator count or capacity in the record we hold. |
| Pennsylvania Department of Environmental Protection, 36-05169B | Under reviewFiled June 22, 2026 | This permit states no generator count or capacity in the record we hold. |
Homer City Energy Campus
Center Township, Pennsylvania · 2 air permits
Pennsylvania Department of Environmental Protection (Air Quality Program, Northwest Regional Office), 32-00457A
- Status
- Issued · Decided November 18, 2025
- What the permit states
- This permit states no generator count or capacity in the record we hold.
Pennsylvania Department of Environmental Protection (Air Quality Program, Northwest Regional Office), 32-00055
- Status
- Issued · Decided March 14, 2026
- What the permit states
- This permit states no generator count or capacity in the record we hold.
| Permit | Status | What the permit states |
|---|---|---|
| Pennsylvania Department of Environmental Protection (Air Quality Program, Northwest Regional Office), 32-00457A | IssuedDecided November 18, 2025 | This permit states no generator count or capacity in the record we hold. |
| Pennsylvania Department of Environmental Protection (Air Quality Program, Northwest Regional Office), 32-00055 | IssuedDecided March 14, 2026 | This permit states no generator count or capacity in the record we hold. |
xAI Colossus 2 (Memphis, Whitehaven)
Memphis, Tennessee · 1 air permit
Mississippi Department of Environmental Quality (Mississippi Environmental Quality Permit Board), PSD Permit to Construct No. 0680-00119 (Agency Interest No. 12592, PER20250001)
- Status
- Issued · Decided March 11, 2026
- What the permit states
- Generators: 8 ProEnergy 6000PE turbines at 50 MW eachGenerators: 41 simple-cycle natural gas turbinesGenerators: 17 Solar Titan PGM-130 turbines at 16.48 MW eachGenerators: 16 Solar Titan 350 turbines at 35 MW eachGenerator capacity: 1,240.16 MW
| Permit | Status | What the permit states |
|---|---|---|
| Mississippi Department of Environmental Quality (Mississippi Environmental Quality Permit Board), PSD Permit to Construct No. 0680-00119 (Agency Interest No. 12592, PER20250001) | IssuedDecided March 11, 2026 | Generators: 8 ProEnergy 6000PE turbines at 50 MW eachGenerators: 41 simple-cycle natural gas turbinesGenerators: 17 Solar Titan PGM-130 turbines at 16.48 MW eachGenerators: 16 Solar Titan 350 turbines at 35 MW eachGenerator capacity: 1,240.16 MW |
Crusoe Abilene AI factory campus for Microsoft
Abilene, Texas · 1 air permit
Texas Commission on Environmental Quality, 182126; PSDTX1688; GHGPSDTX263
- Status
- Under review · Decided August 5, 2026
- What the permit states
- This permit states no generator count or capacity in the record we hold.
| Permit | Status | What the permit states |
|---|---|---|
| Texas Commission on Environmental Quality, 182126; PSDTX1688; GHGPSDTX263 | Under reviewDecided August 5, 2026 | This permit states no generator count or capacity in the record we hold. |
CyrusOne Medina County campus (Sat14), near Castroville
Medina County, Texas · 1 air permit
Texas Commission on Environmental Quality, PBR Registration No. 184983; RN112507629; Project No. 413308
- Status
- Filed · Decided August 12, 2026
- What the permit states
- This permit states no generator count or capacity in the record we hold.
| Permit | Status | What the permit states |
|---|---|---|
| Texas Commission on Environmental Quality, PBR Registration No. 184983; RN112507629; Project No. 413308 | FiledDecided August 12, 2026 | This permit states no generator count or capacity in the record we hold. |
CyrusOne SAT1, San Antonio
San Antonio, Texas · 1 air permit
Texas Commission on Environmental Quality, Permit No. O4793; RN102414737
- Status
- Issued · Decided March 11, 2026
- What the permit states
- Generators: 5 emergency critical generators (GRP-GENCRIT2: GEN A-2, GEN B-2, GEN C-2, GEN D-1, GEN D-2)Generators: 3 emergency critical generators (GRP-GENCRIT1: GEN A-1, GEN B-1, GEN C-1)Generators: 1 emergency house generator (GEN-HOUSE, ENG9-SAI)
| Permit | Status | What the permit states |
|---|---|---|
| Texas Commission on Environmental Quality, Permit No. O4793; RN102414737 | IssuedDecided March 11, 2026 | Generators: 5 emergency critical generators (GRP-GENCRIT2: GEN A-2, GEN B-2, GEN C-2, GEN D-1, GEN D-2)Generators: 3 emergency critical generators (GRP-GENCRIT1: GEN A-1, GEN B-1, GEN C-1)Generators: 1 emergency house generator (GEN-HOUSE, ENG9-SAI) |
CyrusOne SAT2-SAT4 campus, San Antonio
San Antonio, Texas · 1 air permit
Texas Commission on Environmental Quality, Permit No. O4794; RN110660743
- Status
- Issued · Decided July 8, 2026
- What the permit states
- Generators: 1 emergency house generator at SATIV (GEN IV HOUSE, ENGH1 - SATIV)Generators: 1 emergency house generator at SATIII (GEN III HOUSE, ENGH1 - SATIII)Generators: 8 emergency critical generators at SATIV (GEN IV A1, A2, B1, B2, C1, C2, D1, D2)Generators: 1 emergency house generator at SATII (GEN II HOUSE, ENGH1 - SATII)Generators: 16 emergency critical generators at SATIII (GEN A01 through GEN D04)Generators: 8 emergency critical generators at SATII (GEN II A1, A2, B1, B2, C1, C2, D1, D2)
| Permit | Status | What the permit states |
|---|---|---|
| Texas Commission on Environmental Quality, Permit No. O4794; RN110660743 | IssuedDecided July 8, 2026 | Generators: 1 emergency house generator at SATIV (GEN IV HOUSE, ENGH1 - SATIV)Generators: 1 emergency house generator at SATIII (GEN III HOUSE, ENGH1 - SATIII)Generators: 8 emergency critical generators at SATIV (GEN IV A1, A2, B1, B2, C1, C2, D1, D2)Generators: 1 emergency house generator at SATII (GEN II HOUSE, ENGH1 - SATII)Generators: 16 emergency critical generators at SATIII (GEN A01 through GEN D04)Generators: 8 emergency critical generators at SATII (GEN II A1, A2, B1, B2, C1, C2, D1, D2) |
Google Goodnight campus (Armstrong County)
Claude, Texas · 1 air permit
Texas Commission on Environmental Quality, Proposed Air Quality Permit Number 182880; PSD Permit PSDTX1698; GHG PSD Permit GHGPSDTX268
- Status
- Under review · Filed January 30, 2026
- What the permit states
- This permit states no generator count or capacity in the record we hold.
| Permit | Status | What the permit states |
|---|---|---|
| Texas Commission on Environmental Quality, Proposed Air Quality Permit Number 182880; PSD Permit PSDTX1698; GHG PSD Permit GHGPSDTX268 | Under reviewFiled January 30, 2026 | This permit states no generator count or capacity in the record we hold. |
Google Journey Data Center (Haskell County)
Haskell, Texas · 1 air permit
Texas Commission on Environmental Quality, Permit by Rule Registration No. 182922; Project No. 404672; Regulated Entity RN112372271
- Status
- Filed · Filed February 5, 2026
- What the permit states
- This permit states no generator count or capacity in the record we hold.
| Permit | Status | What the permit states |
|---|---|---|
| Texas Commission on Environmental Quality, Permit by Rule Registration No. 182922; Project No. 404672; Regulated Entity RN112372271 | FiledFiled February 5, 2026 | This permit states no generator count or capacity in the record we hold. |
Google Midlothian data center
Midlothian, Texas · 2 air permits
Texas Commission on Environmental Quality, Federal Operating Permit (Title V) O4262; minor revision Project 38479; RN110495884
- Status
- Under review · Filed November 7, 2025
- What the permit states
- This permit states no generator count or capacity in the record we hold.
Texas Commission on Environmental Quality, Permit by Rule Registration 153622 (30 TAC 106.511 and related rules); CN605692540, RN110495884
- Status
- Filed · Filed March 26, 2026
- What the permit states
- This permit states no generator count or capacity in the record we hold.
| Permit | Status | What the permit states |
|---|---|---|
| Texas Commission on Environmental Quality, Federal Operating Permit (Title V) O4262; minor revision Project 38479; RN110495884 | Under reviewFiled November 7, 2025 | This permit states no generator count or capacity in the record we hold. |
| Texas Commission on Environmental Quality, Permit by Rule Registration 153622 (30 TAC 106.511 and related rules); CN605692540, RN110495884 | FiledFiled March 26, 2026 | This permit states no generator count or capacity in the record we hold. |
Google Red Oak data center
Red Oak, Texas · 2 air permits
Texas Commission on Environmental Quality, Project 37459; Title V Permit O4709 application; RN110852753; CN605700061
- Status
- Filed · Decided January 24, 2025
- What the permit states
- This permit states no generator count or capacity in the record we hold.
Texas Commission on Environmental Quality, Federal Operating Permit (Title V) O4709; RN110852753
- Status
- Issued · Decided March 27, 2026
- What the permit states
- This permit states no generator count or capacity in the record we hold.
| Permit | Status | What the permit states |
|---|---|---|
| Texas Commission on Environmental Quality, Project 37459; Title V Permit O4709 application; RN110852753; CN605700061 | FiledDecided January 24, 2025 | This permit states no generator count or capacity in the record we hold. |
| Texas Commission on Environmental Quality, Federal Operating Permit (Title V) O4709; RN110852753 | IssuedDecided March 27, 2026 | This permit states no generator count or capacity in the record we hold. |
Lancium Clean Campus data centers (Crusoe)
Abilene, Texas · 3 air permits
Texas Commission on Environmental Quality, Standard Permit Registration No. 177263 (Project No. 387309)
- Status
- Approved · Decided January 22, 2025
- What the permit states
- Generator capacity: 360.5 MWGenerator capacity: 34.1 MW per GE LM2500 turbine (site-rated)Generator capacity: 38 MW per Titan 350 turbine (site-rated)
Texas Commission on Environmental Quality, Permit No. 182126 / PSDTX1688 / GHGPSDTX263
- Status
- Under review · Filed November 7, 2025
- What the permit states
- This permit states no generator count or capacity in the record we hold.
Texas Commission on Environmental Quality, Permit No. 182126 / PSDTX1688 / GHGPSDTX263
- Status
- Under review · Decided August 5, 2026
- What the permit states
- This permit states no generator count or capacity in the record we hold.
| Permit | Status | What the permit states |
|---|---|---|
| Texas Commission on Environmental Quality, Standard Permit Registration No. 177263 (Project No. 387309) | ApprovedDecided January 22, 2025 | Generator capacity: 360.5 MWGenerator capacity: 34.1 MW per GE LM2500 turbine (site-rated)Generator capacity: 38 MW per Titan 350 turbine (site-rated) |
| Texas Commission on Environmental Quality, Permit No. 182126 / PSDTX1688 / GHGPSDTX263 | Under reviewFiled November 7, 2025 | This permit states no generator count or capacity in the record we hold. |
| Texas Commission on Environmental Quality, Permit No. 182126 / PSDTX1688 / GHGPSDTX263 | Under reviewDecided August 5, 2026 | This permit states no generator count or capacity in the record we hold. |
Meta Fort Worth Data Center
Fort Worth, Texas · 2 air permits
Texas Commission on Environmental Quality, Federal Operating Permit (Title V) O4280; RN108641507; CN604890723
- Status
- Issued · Decided August 4, 2021
- What the permit states
- This permit states no generator count or capacity in the record we hold.
Texas Commission on Environmental Quality, Title V renewal and revision application, Project 39681; Permit 4280
- Status
- Under review · Filed October 13, 2025
- What the permit states
- This permit states no generator count or capacity in the record we hold.
| Permit | Status | What the permit states |
|---|---|---|
| Texas Commission on Environmental Quality, Federal Operating Permit (Title V) O4280; RN108641507; CN604890723 | IssuedDecided August 4, 2021 | This permit states no generator count or capacity in the record we hold. |
| Texas Commission on Environmental Quality, Title V renewal and revision application, Project 39681; Permit 4280 | Under reviewFiled October 13, 2025 | This permit states no generator count or capacity in the record we hold. |
Microsoft San Antonio data centers
San Antonio, Texas · 1 air permit
Texas Commission on Environmental Quality, Permit No. O4781
- Status
- Under review
- What the permit states
- Generators: 31 emergency enginesGenerators: 27 emergency enginesGenerators: 31 emergency engines
| Permit | Status | What the permit states |
|---|---|---|
| Texas Commission on Environmental Quality, Permit No. O4781 | Under review | Generators: 31 emergency enginesGenerators: 27 emergency enginesGenerators: 31 emergency engines |
QTS Irving 1
Irving, Texas · 1 air permit
Texas Commission on Environmental Quality, O4771
- Status
- Under review
- What the permit states
- Generators: 4 diesel-fired house generators (DC3HSE, DC4HSE, DC5HSE, DC6HSE)Generators: 120 diesel-fired emergency generators (EGEN1 through EGEN120) at data center buildings DC1 through DC6
| Permit | Status | What the permit states |
|---|---|---|
| Texas Commission on Environmental Quality, O4771 | Under review | Generators: 4 diesel-fired house generators (DC3HSE, DC4HSE, DC5HSE, DC6HSE)Generators: 120 diesel-fired emergency generators (EGEN1 through EGEN120) at data center buildings DC1 through DC6 |
Vantage TX1 campus, San Antonio (TX11 and TX12)
San Antonio, Texas · 1 air permit
Texas Commission on Environmental Quality, Permit No. O4791; RN111852240
- Status
- Under review
- What the permit states
- Generators: 86 diesel emergency generators at full build-out
| Permit | Status | What the permit states |
|---|---|---|
| Texas Commission on Environmental Quality, Permit No. O4791; RN111852240 | Under review | Generators: 86 diesel emergency generators at full build-out |
Meta Eagle Mountain Data Center
Eagle Mountain, Utah · 1 air permit
Utah Division of Air Quality, DAQE-NN163220001-26
- Status
- Under review · Filed August 30, 2026
- What the permit states
- This permit states no generator count or capacity in the record we hold.
| Permit | Status | What the permit states |
|---|---|---|
| Utah Division of Air Quality, DAQE-NN163220001-26 | Under reviewFiled August 30, 2026 | This permit states no generator count or capacity in the record we hold. |
How to read these figures
Each figure belongs to one permit, and a project can hold several permits: an original permit, an amendment, a renewal, a permit for one building among several. One fleet can be named under more than one permit for the same site. For both reasons the counts on this page are never added together, across permits or across projects.
A generator count prints with the permit's own words for what was counted: the engine type and fuel, and the rating of each unit where the permit states it, such as 2,750 ekW each. Those per-unit ratings are never multiplied by the count on this page. Where a permit states the fleet's capacity itself, in megawatts, that stated figure is printed as the capacity.
Generator capacity is not the data center's announced capacity. It states what the backup fleet can produce, not the load the building draws, and the two are never swapped: the ranking of projects by announced capacity leaves generator figures out.
Of the 237 permits listed, 88 state a generator count and 44 state a generator capacity; 146 state neither in the record we hold. 110 of the permits are entries on the Virginia Department of Environmental Quality's issued-permits index: the index names the site, the registration number, and the date, and publishes no per-permit document, and the department directs readers to its regional offices for individual permits. Those entries are marked on their rows, and there is no original document for us to read generator facts from.
A project with no permit here is a project whose air permit the public record we have found does not hold. Of the 1,320 projects we track, 195 hold at least one air permit.
The rest of the record for these projects
Backup power is one part of what a data center means for the place it lands in. Each project above has its own page, carrying the rest of its record from the same public sources: the jobs it committed to, the tax agreements it signed, and what officials and residents said about it. 24 of the 195 projects hold at least one tax agreement on record. 25 of them also carry an impact record covering property tax, tax breaks, electricity, water, jobs, community, neighbors, and voice.
This page sits under What it means for locals. The projects are ranked by the load they draw on largest projects by announced capacity, which leaves generator figures out on purpose. Grid load growth by state keeps the load figures utilities and grid operators state, measured water use keeps the water figures operators publish, and the record's rankings sit on lists from the record. Each project's own page lists its permits in full, with every fact they state.
What the record shows · November 28, 2026
Loudoun County data centers: the complete record
Loudoun County's 128 data centers paid $684.8 million in equipment tax in fiscal 2024, at the full county rate. The record, from the county's books.
What the record shows · November 22, 2026
SpaceX's SEC filing counts 220,000 processors at xAI Colossus 2, switched on in 91 days and 64 days
Per SpaceX's Form 424B4, xAI Colossus 2 in Memphis runs two clusters online: about 110,000 GB200 processors at about 210 MW, and 110,000 GB300 processors at 220 MW, 430 MW in total.
Questions people ask
- How many backup generators does a data center have?
- As many as the site is built to need, and the air permit is where the number becomes public. The largest single generator count a permit on this page states is 544 engine-generator sets, at QTS Richmond Data Center. Counts run from a single portable unit to fleets in the hundreds, and each count on this page is printed with the permit that states it.
- Why do data centers keep so many generators?
- The generators are the site's backup power. When the grid feed fails, the engines carry the building until power returns, so a large site permits a fleet rather than one machine: engines can be serviced in rotation, and the fleet covers the buildings in groups. The permits call them emergency generators, and they are permitted for that job, not for everyday power.
- Is generator capacity the same as a data center's capacity?
- No. Generator capacity states how much power the backup fleet can produce; announced capacity states the load the data center itself draws. The two measure different things, and this site never uses one for the other: the ranking of projects by announced capacity leaves generator figures out for exactly that reason. Where a permit states a fleet figure, it is printed here as the permit states it: the largest on this page is 1,240.16 MW, at xAI Colossus 2 (Memphis, Whitehaven). A capacity is never computed on this page by multiplying a generator count by a per-unit rating.
- Why do so many permits state no generator count?
- A permit appears here with the facts its document states, and many permits are written around emissions limits and run hours rather than the fleet itself: 146 of the 237 permits state neither a generator count nor a generator capacity in the record we hold. 110 of them are a different case: they are entries on the Virginia Department of Environmental Quality's issued-permits index, a table that names the site, the registration number, and the date but publishes no per-permit document. The department directs readers to its regional offices for individual permits, so there is no original document for us to read a generator count from. Those entries are marked on their rows.
- Do the generators run all the time?
- No. The permits class these engines as emergency generators: they run for testing and maintenance and when the grid feed fails. 9 of the permits on this page also state a cap on run hours in the record we hold, and each project's page prints the caps its permits state.
Sources
- 1Construction Permit 25DG0038 (Issuance 1), EdgeConneX, Inc., Denver Campus
Colorado Department of Public Health and EnvironmentTier 1 · Open the source - 2Air Quality Permit No. 7376-097-0097-S-01-0: Microsoft Corporation - FTY01 Facility, Douglasville, Douglas County
Georgia Environmental Protection Division, Air Protection BranchTier 1 · Open the source - 3Title V Operating Permit 16-TV-002R1, Gable Corporation, 10420 Bunge Ave., Council Bluffs, IA 51503 (Iowa DNR Air Quality Bureau, issued September 7, 2021)
Iowa Department of Natural ResourcesTier 1 · Open the source - 4Title V Operating Permit 18-TV-007R1, Siculus, Inc., 100 Share Way, Altoona, IA 50009 (Iowa DNR Air Quality Bureau)
Iowa Department of Natural ResourcesTier 1 · Open the source - 5Iowa DNR Title V Operating Permit 24-TV-005, Willow Creek / Ginger East Data Centers (Microsoft), issued December 9, 2024
Iowa Department of Natural ResourcesTier 1 · Open the source - 6Iowa DNR Title V Operating Permit 26-TV-003, Microsoft Ginger West Data Center, issued April 10, 2026
Iowa Department of Natural ResourcesTier 1 · Open the source - 7Iowa DNR Title V Operating Permit 24-TV-004, Osmium Data Center (Microsoft), issued October 17, 2024
Iowa Department of Natural ResourcesTier 1 · Open the source - 8Synthetic Minor Source Permit to Construct AAIR16-0082, Apple, Inc. (issued June 13, 2025)
Northern Nevada Public Health, Air Quality Management DivisionTier 1 · Open the source - 9NDEP Class II Air Quality Operating Permit AP7374-5002, Colovore Reno 1 LLC (Facility ID A2675)
Nevada Division of Environmental ProtectionTier 1 · Open the source - 10Class I Air Quality Operating Permit to Construct AP7375-3672, Facility ID A1896, issued to Switch, Ltd.
Nevada Division of Environmental Protection, Bureau of Air Pollution ControlTier 1 · Open the source - 11Draft Air Pollution Control Preconstruction Permit and Certificate to Operate, PN-DC 1, Permit Activity PCP250001, Program Interest 19525
New Jersey Department of Environmental Protection, Bureau of Stationary SourcesTier 1 · Open the source - 12Standard Air Contaminant Discharge Permit No. 34-0235-ST-01, NTT Global Data Centers HI, LLC, Hillsboro
Oregon Department of Environmental QualityTier 1 · Open the source - 13Plan Approval 09-0261 (Phase 1), Amazon Data Services Inc, Falls Township
Pennsylvania Department of Environmental ProtectionTier 1 · Open the source - 14Proposed Plan Approval 09-0261A (Phase 2)
Pennsylvania Department of Environmental ProtectionTier 1 · Open the source - 15Air Pollution Control Permit and Prevention of Significant Deterioration (PSD) Authority to Construct Air Emissions Equipment, Permit No. 0680-00119, MZX Tech LLC, issued March 11, 2026
Mississippi Department of Environmental QualityTier 1 · Open the source - 16Response to Comments and Preliminary Determination, MZX Tech LLC, PSD Permit to Construct No. 0680-00119 (complete packet)
Mississippi Department of Environmental QualityTier 1 · Open the source - 17Federal Operating Permit O4793, CyrusOne SAT1 (issued March 11, 2026)
Texas Commission on Environmental QualityTier 1 · Open the source - 18Federal Operating Permit O4794, CyrusOne SAT2 SAT3 SAT4 (issued July 8, 2026)
Texas Commission on Environmental QualityTier 1 · Open the source - 19Technical Review, Standard Permit Registration No. 177263 (Project No. 387309), Longhorn Data Center
Texas Commission on Environmental QualityTier 1 · Open the source - 20Statement of Basis, Federal Operating Permit O4781, Microsoft SAT15 SAT16 SAT17
Texas Commission on Environmental QualityTier 1 · Open the source - 21Statement of Basis, Federal Operating Permit O4771, QTS Irving (Quality Investment Properties Irving, LLC)
Texas Commission on Environmental QualityTier 1 · Open the source · Archived copy - 22Statement of Basis, Federal Operating Permit O4791, Vantage TX 11
Texas Commission on Environmental QualityTier 1 · Open the source
Back to What it means for locals
Cite this page
Copy this citation when you reuse a figure or a finding from this page.
Data Center Fact Check. "On-site generation." Updated 2026-11-29. Accessed 2026-11-29. https://datacenterfactcheck.org/benefits/on-site-generation