PG&E Advice Letter 7919-E: transmission upgrades for GIC San Jose LLC (Tier 3, resolution required)

Where it stands: Pending before the commission as of May 26, 2026

Draft research, not yet verified. Open a source to check any detail.

What it is

PG&E's Tier 3 Advice Letter 7919-E (May 26, 2026) asks for approval of transmission upgrades for GIC San Jose LLC, which requested transmission-level electric service for a data center at 350 W Trimble Rd, San Jose with a maximum forecasted demand of 97.3 MW. The Q5 WG2 sweep put the estimated transmission upgrade cost at $58,280,000 including ITCC, plus $10,726,000 of special facilities (a new 115 kV switching station and a redundant 115 kV line), with facilities expected operational in the third quarter of 2028. No resolution disposing of the advice letter had been located as of the Q5 sweep, so the matter is rowed as pending.

The facts

Regulator
California Public Utilities Commission
Docket number
Advice Letter 7919-E
Type
Other
Utility
Pacific Gas & Electric Co.
State
California
Filed
May 26, 2026
Status date
May 26, 2026
Large-load rules
Yes, for loads of 97.3 MW or more

Projects served by Pacific Gas & Electric Co.

Related cases and proceedings

In the record

  1. Utility case, May 26, 2026. Utility case filed: PG&E Advice Letter 7919-E: transmission upgrades for GIC San Jose LLC (Tier 3, resolution required) California Public Utilities Commission, Advice Letter 7919-E

Sources

  1. 1
    Advice 7919-E: Electric Rules 2, 15, and 16 Exceptional Case Submittal for Electric Transmission Upgrades for GIC San Jose LLC
    Pacific Gas and Electric Company (CPUC advice letter)
    Tier 2 · Advice Letter 7919-E (PG&E, dated May 26, 2026): GIC San Jose LLC requested transmission-level electric service for a data center at 350 W Trimble Rd., San Jose, with a maximum forecasted demand of 97.3 MW. Cost and schedule figures are per the Q5 WG2 notes on the same advice letter. · Open the source

Report an error or send a tip on this page