SB 26-102: Sets renewable power and grid cost rules for large data centers
Official title: Large-Load Data Centers
Draft research, not yet verified: traced to the official record by an AI research agent; an editor has not checked it yet.
Where it stands
Died or failed as of May 11, 2026. The official record says: Died in Senate Transportation & Energy.
- Filed (done)
- In committee (not reached)
- Passed one chamber (not reached)
- Passed both chambers (not reached)
- Signed into law (not reached)
- In effect (not reached)
- Died or failed (current stage)
What it does
Contract term
Applies to: large-load data center operators using utility power supply (Colorado)
“THROUGH CONTRACTS WITH UTILITIES OF AT LEAST FIFTEEN YEARS, IF USING UTILITY POWER SUPPLY, A LARGE-LOAD DATA CENTER OPERATOR SHALL PAY FOR ... ALL OF THE COSTS ASSOCIATED WITH A UTILITY CONSTRUCTING OR PROCURING GENERATION, TRANSMISSION, AND DISTRIBUTION INFRASTRUCTURE NECESSARY TO SUPPLY THE OPERATOR'S LARGE-LOAD DATA CENTER WITH ELECTRICITY.”
Introduced text, section 2, new C.R.S. 40-2.5-103(4)
Definition · threshold 30 MW
Applies to: data centers beginning or expanding operation on or after the act's effective date (Colorado)
“"LARGE-LOAD DATA CENTER" MEANS: (a) A DATA CENTER THAT BEGINS OPERATION ON OR AFTER THE EFFECTIVE DATE OF THIS SECTION: (I) WITH A PEAK LOAD OF MORE THAN THIRTY MEGAWATTS; OR (II) THAT IS COVERED BY AN INTERCONNECTION AGREEMENT THAT ALLOWS FOR A PEAK LOAD OF MORE THAN THIRTY MEGAWATTS; (b) MULTIPLE DATA CENTERS THAT BEGIN OPERATION ON OR AFTER THE EFFECTIVE DATE OF THIS SECTION AND THAT: (I) HAVE A COLLECTIVE PEAK LOAD OF MORE THAN SIXTY MEGAWATTS; [and existing data centers that add the same amounts].”
Introduced text, section 2, new C.R.S. 40-2.5-101(6)
Demand response
Applies to: utilities (Colorado)
“A UTILITY SHALL DEVELOP AND OFFER AT LEAST ONE OF THE FOLLOWING TO THE UTILITY'S CUSTOMERS THAT ARE LARGE-LOAD DATA CENTER OPERATORS: (I) ONE OR MORE DEMAND RESPONSE PROGRAMS ... THAT ENCOURAGE LARGE-LOAD DATA CENTER OPERATORS TO SIGNIFICANTLY REDUCE THE POWER DEMAND OF THE OPERATOR'S LARGE-LOAD DATA CENTER DURING PEAK PERIODS THROUGH LOAD-SHIFTING, BATTERY STORAGE, UNINTERRUPTIBLE POWER SUPPLY, OR ON-SITE OR ZERO-EMISSIONS BACKUP GENERATION; OR (II) FLEXIBLE CONNECTION TARIFFS OR OTHER TARIFFS THAT ENCOURAGE OR REQUIRE LARGE-LOAD DATA CENTER OPERATORS TO SIGNIFICANTLY REDUCE THE POWER DEMAND OF THE OPERATOR'S LARGE-LOAD DATA CENTER DURING PEAK PERIODS.”
Introduced text, section 2, new C.R.S. 40-2.5-105(5)(a)
Electric rate class
Applies to: utilities (Colorado)
“A UTILITY SHALL NOT OFFER ECONOMIC DEVELOPMENT RATES PURSUANT TO SECTION 40-3-104.3 TO LARGE-LOAD DATA CENTERS.”
Introduced text, section 2, new C.R.S. 40-2.5-105(4)
Study or report
Applies to: the public utilities commission (Colorado)
Ends: 2030-06-30.
“NO LATER THAN JUNE 30, 2030, THE COMMISSION SHALL, IN CONSULTATION WITH THE OFFICE AND THE AIR POLLUTION CONTROL DIVISION IN THE DEPARTMENT OF PUBLIC HEALTH AND ENVIRONMENT AND FOLLOWING A NONADJUDICATORY PROCEEDING WITH THE OPPORTUNITY FOR PUBLIC INPUT, MAKE A DETERMINATION ON WHETHER ONE-HUNDRED-PERCENT HOURLY MATCHING BY LARGE-LOAD DATA CENTERS IS TECHNICALLY AND ECONOMICALLY FEASIBLE.”
Introduced text, section 2, new C.R.S. 40-2.5-102(1)
Who pays for grid costs
Applies to: utilities serving large-load data centers (Colorado)
“A UTILITY SHALL NOT INTERCONNECT OR SUPPLY ELECTRICITY TO A LARGE-LOAD DATA CENTER UNLESS THE LARGE-LOAD DATA CENTER OPERATOR HAS EITHER FIRST PROVIDED AN UP-FRONT PAYMENT OR ENTERED INTO A CONTRACT OF AT LEAST FIFTEEN YEARS WITH THE UTILITY, WHICH UP-FRONT PAYMENT OR CONTRACT MUST REQUIRE THE OPERATOR TO PAY FOR ... ALL OF THE COSTS ASSOCIATED WITH THE UTILITY CONSTRUCTING OR PROCURING GENERATION, TRANSMISSION, AND DISTRIBUTION INFRASTRUCTURE NECESSARY TO SUPPLY THE OPERATOR'S LARGE-LOAD DATA CENTER WITH ELECTRICITY.”
Introduced text, section 2, new C.R.S. 40-2.5-105(2)(a)
Service terms
Applies to: large-load data center operators (Colorado)
Starts: 2031-01-01.
“A LARGE-LOAD DATA CENTER OPERATOR SHALL, BEGINNING JANUARY 1, 2031: (a) GENERATE, PURCHASE, OR OTHERWISE ACQUIRE A QUANTITY OF ELECTRICITY GENERATED FROM RENEWABLE RESOURCES NECESSARY TO MEET ONE HUNDRED PERCENT OF THE OPERATOR'S LARGE-LOAD DATA CENTER'S TOTAL ANNUAL ELECTRICITY CONSUMPTION FOR EACH YEAR THAT THE LARGE-LOAD DATA CENTER IS OPERATIONAL; (b) [acquire renewable electricity and credits sufficient] TO ACHIEVE AT LEAST THE HIGHEST PERCENTAGE OF HOURLY MATCHING THAT THE COMMISSION DETERMINES IS TECHNICALLY AND ECONOMICALLY FEASIBLE FOR LARGE-LOAD DATA CENTERS PURSUANT TO SECTION 40-2.5-102.”
Introduced text, section 2, new C.R.S. 40-2.5-103(1)
Reporting duty
Applies to: large-load data center operators (Colorado)
Starts: 2028-06-30.
“NO LATER THAN JUNE 30, 2028, AND NO LATER THAN EACH JUNE 30 THEREAFTER, A LARGE-LOAD DATA CENTER OPERATOR SHALL REPORT TO THE DEPARTMENT OF PUBLIC HEALTH AND ENVIRONMENT THE FOLLOWING INFORMATION FOR THE PREVIOUS CALENDAR YEAR FOR THE OPERATOR'S LARGE-LOAD DATA CENTER: (a) TOTAL ANNUAL ELECTRICITY CONSUMPTION; (b) PEAK LOAD; ... (j) TOTAL ANNUAL WATER CONSUMPTION ...; (n) THE TOTAL AMOUNT OF INCENTIVES OR SUBSIDIES RECEIVED BY THE LARGE-LOAD DATA CENTER OPERATOR FROM LOCAL GOVERNMENTS, ECONOMIC DEVELOPMENT ORGANIZATIONS, OR OTHER ENTITIES.”
Introduced text, section 2, new C.R.S. 40-2.5-104(1)
Site assessment
Applies to: large-load data center developers (Colorado)
“WITH ITS DEVELOPMENT PERMIT APPLICATION FOR A LARGE-LOAD DATA CENTER, A LARGE-LOAD DATA CENTER DEVELOPER SHALL SUBMIT A SITE ASSESSMENT TO THE LOCAL GOVERNMENT REVIEWING THE DEVELOPMENT PERMIT APPLICATION. A SITE ASSESSMENT MUST INCLUDE DESCRIPTIONS OF: (a) ANTICIPATED TOTAL WATER FOOTPRINT, INCLUDING DIRECT AND INDIRECT WATER USAGE AND TOTAL WATER INPUT IN CUBIC METERS; (b) PLANNED WATER SOURCES ...; (c) ANTICIPATED ON-SITE AIR EMISSIONS ...; (f) A DESCRIPTION OF INITIAL AND ONGOING OPPORTUNITIES FOR PUBLIC ENGAGEMENT.”
Introduced text, section 2, new C.R.S. 40-2.5-106(2)
Who it touches
No project we track is matched to this bill or order: its rules do not reach them, or a check found it does not apply.
Other projects we track in Colorado (34), not affected
- 365 Data Centers Aurora (CO1)Operating
- Aerotropolis Logistics Center data center (Aurora application)Proposed
- BluSky AI Walsenburg data centerAnnounced
- Centersquare DEN2Operating
- Cielo Hudson data center campusProposed
- CoreSite DE3 (Race Street campus)Under construction
- CoreSite Denver data centers (DE1, DE2)Operating
- DataBank DEN1 (Denver)Operating
- DataBank DEN1 (Englewood)Operating
- DataBank DEN2 (Centennial)Operating
- DataBank DEN3 (Downtown Denver)Operating
- DataBank DEN4 (Denver)Operating
- DataBank DEN4 (Westminster)Operating
- DataBank DEN5 (Centennial II)Operating
- DataBank DEN5 (Denver)Operating
- EdgeConneX Denver CampusExpanding
- Equinix Denver data centers (DE1, DE2)Operating
- Flexential Aurora data centerOperating
- Flexential Centennial data centerOperating
- Flexential Denver-Parker data centerUnder construction
- Flexential Englewood data centerOperating
- Fontus Data Centre ProjectAnnounced
- Global AI data center (Weld County)Approved
- H5 Data Centers Denver campusOperating
- Iron Mountain Data Centers Iron Mountain Denver (Denver)Operating
- Iron Mountain DEN-1 (Denver)Operating
- Northeast Brighton data center campus (withdrawn application)Cancelled
- Novva Data Centers Colorado SpringsOperating
- NTT Global Data Centers AuroraAnnounced
- OneNeck Denver Data CenterOperating
- QTS Aurora-Denver data center campus (Denver 1)Under construction
- QTS Colorado Springs data centerOperating
- Raeden Project Taurus (Colorado Springs)Approved
- Vantage Trident data center campusIn permitting
Who acted
- Primary sponsorKippSenate
- SponsorBrownHouse
More from Colorado
- HB 26-1030 · Died or failedCreates a data center authority and 20-year sales tax exemption
- SB 25-280 · Died or failedCreates tax exemptions and grid planning for certified data centers
- SB 24-085 · Died or failedSales and use tax rebate for data center (digital asset) purchases
- SB 23-207 · Died or failedSales and use tax refund for data center purchases
Sources
- 1
- 2Senate Bill 26-102, introduced text (LLS No. 26-0017.03)