Skip to content

Utility commission

Petition of Rappahannock Electric Cooperative For approval to implement a new Large Power Dedicated Facilities Rate Schedule

Where it stands: In effect as of Jul 1, 2025

Draft research, not yet verified. Open a source to check any detail.

What it is

Schedule LP-DF is mandatory for very large, high load factor customers served through dedicated facilities: contracted billing demand over 25 MW, average annual load factor of at least 75 percent, service through a dedicated substation at 34.5 kV or greater from a transmission delivery point of 115 kV or higher, under an Electric Service Agreement executed no later than 12 months before the desired service date. The ESA term is negotiable but must recover the full cost of the distribution and sub-transmission plant investment, with credit collateral support as the Cooperative determines; the customer remains responsible for capacity and transmission charges after discontinuing service, pays upfront CIAC for power factor correction and excess facilities, a monthly fixed charge of 0.92 percent of substation investment, and a minimum distribution charge set in the ESA.

The facts

Regulator
Virginia State Corporation Commission
Docket number
PUR-2025-00048
Type
Large load tariff
Utility
Rappahannock Electric Cooperative
State
Virginia
Filed
Mar 12, 2025
Status date
Jul 1, 2025
Large-load rules
Yes, for loads of 25 MW or more

Related cases and proceedings

In the record

  1. Utility case, Mar 12, 2025. Utility case filed: Petition of Rappahannock Electric Cooperative For approval to implement a new Large Power Dedicated Facilities Rate Schedule Virginia State Corporation Commission, PUR-2025-00048

Sources

  1. 1
    Schedule LP-DF, Large Power Dedicated Facilities Rate Schedule (SCC accepted for filing January 29, 2026; effective July 1, 2025)
    Rappahannock Electric Cooperative
    Tier 1 · Schedule LP-DF, Section II (applicability: ESA timing, dedicated substation, 25 MW, 75 percent load factor, ESA term and collateral), Section IV.C (charges after discontinuance; power supply credit collateral), Sections V-VII (CIAC; 0.92 percent substation charge; minimum distribution charge) · Open the source

Report an error or send a tip on this page

Cite this page

Copy this citation when you reuse a figure or a finding from this page.

Data Center Fact Check. "Petition of Rappahannock Electric Cooperative For approval to implement a new Large Power Dedicated Facilities Rate Schedule." Last activity 2025-07-01. Accessed 2026-11-29. https://datacenterfactcheck.org/dockets/utility/proc-rappahannock-lp-df-2025